Voltage Drop Calculator

instant voltage drop and end voltage

  • Free
  • Runs in your browser
  • No account needed

This calculator gives voltage drop, percent drop, end voltage and conductor resistance. Example: a 30 m run of 4 mm2 copper at 20 A on 230 V drops about 5.17 V, or 2.25%.

Voltage drop
4.41 V
Voltage drop percent
1.92%
Voltage at the load
225.6 V
Resistance of one conductor
0.1379 ohms
Compared with common limits
Up to 3%: within the usual 3% guide for lighting and branch circuits.

The US NEC suggests (in an informational note) up to 3% for a branch circuit and 5% in total; BS 7671 uses 3% for lighting and 5% for other uses. Wire size must also meet the current rating and your local wiring rules. A licensed electrician should design and check real installations.

Runs in your browser. Your files and values are not sent to us. Report a problem
Advertisement

About the Voltage Drop Calculator

You use this tool to estimate voltage loss along a conductor for simple DC, single-phase or three-phase systems. Enter circuit type, conductor metal, wire size, one-way length and unit, current, supply voltage and conductor temperature. The tool computes one-conductor resistance, voltage drop in volts, percent drop and voltage at the load. It ignores reactance and power factor, which is fine for short runs or resistive loads but not for long motor feeders. Calculations use resistivity values and temperature correction so results update instantly in your browser with no upload. You can copy results and share a link that reopens with your numbers. The page compares the result with common guidance from NEC and BS 7671 and reminds you that wire ampacity and local rules still apply.

How to use it

  1. 1Select circuit type, conductor metal and wire size.
  2. 2Enter one-way length, units, current, supply voltage and conductor temperature.
  3. 3Read resistance, voltage drop, percent drop and voltage at the load.
  4. 4Copy results or create a share link that reopens with your numbers.
Advertisement

Worked example

Inputs: Single-phase, Copper, 4 mm2, One-way length 30 m, Current 20 A, Supply voltage 230 V, Conductor temperature 20 C. Results: Resistance of one conductor = 0.12931 ohm, Voltage drop = 5.17 V, Drop = 2.25%, Voltage at load = 224.83 V. Compared with common limits: Pass for 3% branch limit.

The formula

Resistance of one conductor R = resistivity x length / cross-section areaResistivity at 20 C: copper 0.017241 ohm mm2/m (IEC annealed copper standard), aluminium 0.028264, adjusted by 1 + alpha x (temperature - 20) with alpha 0.00393 (copper) or 0.00403 (aluminium)Drop = 2 x I x R for single-phase or DC, square root of 3 x I x R for three-phase (line to line)AWG areas come from circular mils (1 cmil = 0.0005067 mm2)Reactance is ignored, which is fine for small cablesCaveat shown on the page: The US NEC suggests (in an informational note) up to 3% for a branch circuit and 5% in total; BS 7671 uses 3% for lighting and 5% for other usesWire size must also meet the current rating and your local wiring rulesA licensed electrician should design and check real installationsResults update instantly as the visitor types; there is no calculate buttonVisitors can copy the result and share a link that reopens with their numbers

Source: NFPA 70 (NEC) information on voltage dropIEC 60364-5-52 (Annex G) guidance on voltage drop. Last checked 13 November 2026.

What it is good for

  • Shows volts, percent drop and voltage at the load instantly as you type.
  • Supports AWG and mm2 sizes and copper or aluminium conductors.
  • Runs in your browser with shareable links and copyable results.
  • Reactance and power factor are ignored, so results are estimates for short resistive runs.
  • Wire ampacity and local rules are not checked; a licensed electrician must verify final designs.
Advertisement

Questions people ask

What inputs do I need to use this calculator?

You enter circuit type, conductor metal, wire size, one-way length and unit, current, supply voltage and conductor temperature. The tool updates results instantly with those inputs.

Does the tool include AC reactance or power factor?

No. The tool ignores reactance and power factor. That assumption is acceptable for short runs and resistive loads, but not for long motor feeders or low power factor loads.

What limits does the tool compare the result with?

The page compares the computed percent drop with common guidance: NEC informational note of 3% for a branch and 5% total, and BS 7671 guidance of 3% for lighting and 5% for other uses.

Are the results exact for installation design?

Results are estimates based on conductor resistivity and temperature correction. Wire ampacity, installation method and local rules still apply. Have a licensed electrician check installations.

Can I save or share my calculation?

Yes. You can copy the numeric result and create a share link that reopens the page with your inputs. The tool runs in your browser and needs no account.

Which units and wire sizes does the calculator support?

The calculator supports metric mm2 sizes and a set of AWG sizes with circular mil conversions. You choose metres or feet for length and the tool converts areas internally.

Help keep every tool free

FreeToolr stays free because people help it grow. Share a tool you like, tell us what to build next, or support us on Ko-fi.

Advertisement
Advertisement